FBD说明书(English)

来源:六九路网


FBD series fan

manual

Sichuan Tongli Machinery Co Ltd

China

1 introduction

FBD series of coal mine explosion-prooftype pressure into the rotary axial flowlocal fan (hereinafter referred to as thefan), is a relatively long distance tunnel excavation use of a new type of ventilation equipment, mainly used in coal mines need to be larger, the higher the pressure of the excavation face ventilation.

Ventilation machine design, manufacturingand inspection, in line with the coal mine MT222-2007< local ventilation machine technology conditions > coal industry standard, and Q/680417570.01-2013《FBDseries mining of explosion pressure in type of rotating axial local fan technology condition > all provisions, is a safe, reliable, excellent performance, high efficiency of the ventilator products.

Ventilation machine implementation standards: MT222-2007< coal mine with local fan technical conditions >, and Q/680417570.01-20132 Construction Feature

The ventilator is used for mine explosion proof equipment, explosion-proof type: explosion-proof type; explosion proof mark: ExdI Mb.

The working mode of the ventilator: \"press in type\" ventilation.

The fan is composed of a wind turbine with an acoustic structure of a body and a two body, an impeller, a two stage impeller, an acoustic diffuser cone, and a wind turbine with a three phase induction motor (see Figure 1):

1、horn mouth2、first state3、first stage impeller 4、second stage impeller 5、second stage 6、 motor 7、Silent release pressure cone tube Fig. 1 Schematic diagram of the structure

The impeller of the fan is made of the impeller of the circular arc blade, the two stage is relative rotation and the two stage is the guide vane, which saves the guide vane, avoids the guide vanes, and saves the energy. It can greatly reduce the noise, especially the high frequency noise, improve the supporting plate.

The auxiliary motor of the fan is a type of explosion-proof three-phase asynchronous motor, explosion-proof type: explosion-proof type: explosion-proof symbol:ExdI Mb。

Fan with rubber or plastic positive pressure air duct supporting, composed of ventilation system, the fresh air to the tunneling working surface.

3 Model designation

F B D №X / 2×Y

Machine power (Kw), (Y) single motor power

Machine number (Xdecimeter number of impeller diameter) Common axis reverserotation Explosion proof type Fan

4 basic mechanical design feature

The design of the ventilator can be operated for 13000 hours before the first major overhaul. The air volume, total pressure, total pressure efficiency and other technical performance indexes and the overall dimension of the fan are shown in Table 1, table 2 and figure 1.

5 working environment condition

Under the following conditions, the ventilation function is running continuously in the relevant working condition.

A) above sea level, no more than +1000m; B) ambient air temperature: -15 to +40

C) the relative humidity of the ambient air is not more than 95% (+25). D) without strong vibration and corrosive gas;

E) installed in the underground coal mine ventilation system of a gas explosion hazard within, and supporting the use of positive pressure flexible air duct.

Note: if the use of the above sea level is higher than the +1000m or the highest ambient temperature is higher than the +40, it should be settled according to the provisions of GB755 or the supply and demand sides.

6 installation and trial operation

6.1 the installation and use of the ventilator must comply with the relevant provisions of the safety regulations of coal mine.

6.2 the stator winding insulation performance of the motor should be checked before the well. The insulation resistance of stator windings of the motor should be greater than 50M.

6.3 in the course of transportation and installation of ventilation, it should avoid collision and knock. 6.4 when installation, should check the impeller rotation is flexible, there is no jamming phenomenon. The clearance between the tip and the casing is uniform, gap is in the impeller diameter of 1.5% ~ 3.5% range and not less than 1.0mm.

6.5 fan installation, between the flange connection, should add asbestos rope, or rubber seal, or rubber gasket seal, to prevent air leakage.

6.6 fan and a starter of the installation location must meet the \"coal mine safety regulations\" the relevant provisions, before running connect the inner and outer earth wire.

6.7 according to the motor wiring diagram (Figure 2), the right to access power, so that the direction of the rotation of the impeller with the direction of the body on the direction of signs to indicate the direction.

Figure 2 Schematic diagram

6.8 fans of the first motor and the two motor should be selected with a lack of phase, over current, short circuit and leakage protection of the starting controller as the control device of the ventilator.

6.9 check the fan of the fastener is complete, firm, and shall not have any loose.

6.10 confirm that the fan is stable and reliable, and can be used for trial operation; running time is more than 30 minutes, and the operation of the test run should be carefully observed.

6.11 fan recommended supporting the use of fan outlet diameter is more than 1.2 times the diameter of rubber or plastic positive pressure flexible air duct.

7 note

7.1 is forbidden to open the electric motor terminal box; prohibit the impact and beat the junction box. 7.2 maintenance or dismantle the motor, should pay particular attention to the protection of the explosion-proof surface, flameproof surface should be coated with Vaseline or other industrial antirust oil.

7.3 fan inlet direction in front of 3M range, are not allowed to have a piece of wood, bamboo sticks, wire and other debris and large pieces of paper, cardboard, plastic bags sacks films such as flakes, so as not to be inhaled fan, fan damage, or block the air inlet, the ventilator can't work normally.

8 operation and maintenance

8.1 the operation of ventilation machine should have full-time or part-time staff management, part-time staff management, the two time between the inspections should not exceed 2 hours, the time of inspection shall not be less than 15 minutes.

8.2 management personnel should always check the sound of the ventilation is normal, whether the connection is loose after Fan continuous work 6 months

8.3 consecutive months, should be checked, the replacement of motor bearing grease once; the addition of grease to the bearing chamber of the 1/2.

8.4 when the ventilator is not used, it should be placed on the air flow, dry, non corrosive gas environment. 9 main faults and troubleshooting methods

Fault featuare Fault cause Identifaction and resolution Collision from Fan blade and shell Repair or replace impelle Noise of metal collision Metal particles Motor bearing damage Exclusion of foreign body Replace motor bearing or replace moto

Bearing screaming and Too much grease, insufficient or Reduce or raise grease or clean the not clean Grease aging or model is wrong bearing Replace grease and clean the bearing Reduce grease or replace bearing temperature rising Bearing inside vibration,Collision Excessive grease or bearing fatigue wea Impeller dynamic balance is no Impeller to balance or replace the Fan,motor vibration longer maintained Flange bolt loosening impell Check and tighten the connecting bolts Low aie pressure and less aie flow Vibration Air duct air leakage, impeller turn Check whether the phase leakage, right or the motor speed is not check the impeller, check the steering enough moto Check the inlet and outlet of fan more The ventilator is running under unstable conditions. Motor damage or power off strongly,Intermittent noise one or double impeller stop operation Motoe start difficully Replace electric motor or power on Power supply voltage is too low or Improve the power supply voltage or start controller failure check the boot controlle 10 Schedule 1 main performance indexes of the ventilator Schedule 2 main structural dimensions of ventilation machine

Schedule 1 main performance indexes of the ventilator

Rated Motor mdel power speed/min YBF2-132S1-2 YBF2-132S2-2 YBF2-160M1-2 5.6 YBF2-160M2-2 YBF2-160L-2 6.0 YBF2-160L-2 YBF2-180M-2 YBF2-180M-2 6.3 YBF2-200L1-2 YBF2-200L2-2 7.1 YBF2-200L2-2 YBF2-225M-2 YBF2-200L2-2 7.5 YBF2-225M-2 YBF2-250M-2 8.0 YBF2-250M-2 YBF2-280S-2 YBF2-250M-4 10.0 YBF2-280S-4 YBF2-280M-4 YBF2-280S-4 11.2 YBF2-280M-4 YBF2-315S-4

model № Air volum m/min 3Total pressure Pa 500~2800 700~3400 750~3800 800~4400 850~5000 870~5400 920~5600 920~5800 1000~6200 1050~6400 1150~6600 1200~6700 1180~6700 1200~6800 1400~7000 1400~7600 1450~7700 1000~4800 1100~5000 1200~5200 1100~5500 1200~6000 1450~6500 Efficiency Noise dBcA % 5.0 2×5.5 2×7.5 2×11 2×15 2×18.5 2×18.5 2×22 2×22 2×30 2×37 2×37 2×45 2×37 2×45 2×55 2×55 2×75 2×55 2×75 2×90 2×75 2×90 2×110 2900 2900 2930 2930 2940 2940 2950 2950 2950 2950 2950 2960 2950 2950 2950 2970 2970 1480 1480 1480 1480 1480 1480 190~150 230~175 300~230 340~270 450~300 480~320 500~340 550~350 600~370 650~400 700~430 750~500 750~450 800~500 900~600 950~560 1100~600 1100~750 1180~800 1520~980 1450~950 1800~1100 1950~1250 ≥75 ≥75 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≥80 ≤30 ≤30 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25 ≤25

Schedule 2 main structural dimensions of ventilation machine

Model Impeller diamete ф(mm) Long (mm) Wide L1 (mm) HighH (mm) Hole distance B(mm) A(mm) Inlet diamete ф(mm) Center height (mm) FBD№5.0 500 1700 670 880 460 560 630 360 FBD№5.0 560 2230 740 950 770 780 720 405 FBD№6.0 600 2630 741 1065 810 810 780 440 FBD№6.3 630 2760 795 1100 905 870 820 465 FBD№7.1 710 3260 910 1230 1010 960 865 530 FBD№7.5 750 3285 960 1260 1160 580 960 560 FBD№8.0 800 3670 1025 1325 1020 1010 960 560 FBDFBD№10.0 №11.2 1000 4900 1290 1625 1400 770 1290 800 1120 4940 1440 1745 1400 840 1440 860